Balanced poly phase circuits. Two and four phase systems. A two phase system is an electrical system in which the voltages of the phases are 90 degree out of time phase. The emf’s Eac and Ebd are 90 degree out of time phase.
Share
Transcript
Balanced poly phase circuits Two and four phase systems
  • A two phase system is an electrical system in which the voltages of the phases are 90 degree out of time phase.
  • The emf’sEac and Ebd are 90 degree out of time phase.
  • A two phase system is the equivalent of two separate single-phase systems that are separated 90 degree in time phase.
  • If the connection is made between the two windings at n and n`, the system would be called a four-phase system.
  • The voltages Eda, Eab, Ebc and Ecd are called the line voltages, while voltages E0a, E0b, E0c and E0d are called the phase voltages or voltages to neutral.
  • Eda=Ed0+E0a. Thus, the line voltages= times the phase voltages in the four phase star.
  • Two and four phase systems
  • The line voltages are 45 degree or 135 degree out of time phase from the phase voltages.
  • For four-phase mesh, the aa` line current is Iaa`=Ida+Iba.
  • Thus, the line currents= times the phase currents degree out of time phase in the four phase mesh
  • Three phase four wire systems
  • The line voltages are 45 degree or 135 degree out of time phase from the phase voltages.
  • For four-phase mesh, the aa` line current is Iaa`=Ida+Iba.
  • Thus, the line currents= times the phase currents degree out of time phase in the four phase mesh
  • Three phase four wire system N is the neutral wire. Lighting loads are placed from line to neutral. Motors and other three phase power loads are connected between the three lines. Three phase four wire system Three phase four wire system The current in any line is the same as the current in the corresponding phase. Current in the neutral wire is obtained through the application of KCL. These currents are equal in magnitude and displaced from one another in time phase by 120 degree. Thus the current in the neutral wire is 0 since Three phase three wire system Balanced Wye loads Given the line voltages as 220 volts balanced three phase and R and X of each phase 6 ohms resistance and 8 ohms inductive reactance. Find the line current, power per phase and total power. Draw the vector diagram Balanced Delta loads Given the line voltages as 220 volts balanced three phase and R and X of each phase 6 ohms resistance and 8 ohms inductive reactance. Find the line current, power per phase and total power. Draw the vector diagram self Power calculation in balanced systems Wye connection Dealta connection Volt-Amperes Wye connection Dealta connection Reactive Volt-Amperes Wye connection Dealta connection Single phase and balanced three phase power For any phase a Three wattmeter method Two wattmeter method Two wattmeter method Copper required to transmit power under fixed conditions Copper required to transmit power under fixed conditions Harmonics in balanced three phase wye loads Harmonics in balanced three phase wye loads
  • The fundamental and all harmonics that obtained by adding a multiple of 6 to the fundamental will have the same sequence. These are first, seventh, thirteenth, nineteenth, twenty-fifth and so on.
  • The fifth, elevenths, seventeenths, twenty-thirds have the same sequences but opposite to that of fundamentals.
  • The third, ninth and all multiples of the third will be found to be in phase.
  • Eba is 30 degree ahead of ena. For the third harmonic, eba3=0. fifth, eba5 lags ena5 by 30 degree.
  • Harmonics in balanced three phase wye loads Unbalanced system
  • An unbalanced system is due to unbalanced voltage sources or unbalanced load.In a unbalanced system the neutral current is NOT zero.
  • Unbalanced three phase Y connected load. Line currents DO NOT add up to zero. In= -(Ia+ Ib+ Ic) ≠ 0 Exam-1 unbalanced load. Exam-3 unbalanced load. The unbalanced load.Wye-Wye system with neutral connection Methods of checking voltage phase sequence unbalanced load. The voltage across a lamp The voltage across “c” lamp Example:5 unbalanced load. Two wattmeter method unbalanced load. W1reads W2reads Three Phase Power Measurement unbalanced load. Three-wattmeter method for measuring three-phase power Power factor in unbalanced three phase system unbalanced load. Phase a 283vars 283 watts Phase b 200 watts 250 watts -433vars Phase c Example:11 unbalanced load.
    Related Search
    We Need Your Support
    Thank you for visiting our website and your interest in our free products and services. We are nonprofit website to share and download documents. To the running of this website, we need your help to support us.

    Thanks to everyone for your continued support.

    No, Thanks
    SAVE OUR EARTH

    We need your sign to support Project to invent "SMART AND CONTROLLABLE REFLECTIVE BALLOONS" to cover the Sun and Save Our Earth.

    More details...

    Sign Now!

    We are very appreciated for your Prompt Action!

    x